  • ARC 62604BACHELOR OF ARTS (HONOURS) IN INTERIOR ARCHITECTURE PROFESSIONAL
  • 01 ASSIGNMENT 1GROUP PRESENTATION SPREAD (SPACE LIGHT & VENTILATION) WEEKLY PROGRESS SUBMISSIONS
  • Page 301 ASSIGNMENT 1
  • SPACE, LIGHT & VENTILATIONBY-LAW 35 ACCESS FROM A STREET
  • BY-LAW 37PROJECTIONS OVER THE STREET AND OVER THE BUILDING LINE BY-LAW 39
  • BY-LAW 40AIR-WELLS Skylight to maximize use of natural light.
  • Page 73 This provision apply to building with mechanically ventilated or air conditioned. The provisions of these bylaws regarding natural ventilation and natural lighting shall not apply to lavatories, water closets, bathrooms, or corridors where permanent mechanical ventilation is provided for and maintained in accordance with the requirements of the Third Schedule to these bylaws.
  • DRAFT SUBMISSIONSPACE,LIGHT & VENTILATION
  • Page 9UBBL SPACE,LIGHT & VENTILATION
  • Page 1002 ASSIGNMENT 2
  • QUESTION 1QUESTION 1 INTERIOR DESIGN LICENSURE EXAMINATION
  • QUESTION 1QUESTION 1B QUESTION 1A
  • QUESTION 2QUESTION 2 (30 marks)
  • QUESTION 2QUESTION 28 QUESTION 2A
  • Page 1503 ASSIGNMENT 3
  • SIZE: 893SQFTRENTAL: RM3600/MONTH RENT RATE: RM 4.14 PSF (FLOOR)
  • SERVICE FRAMEWORKMARKETINGS STRATEGIES SPATIAL PLANNING & DESIGN CONSULTANCY (01
  • FUTURE PRACTICEDIGITAL & SMART DESIGN PRACTICE D
  • DRAFT SUBMISSIONSTAMPING MONTHLY EXPENDITURE
  • Page 2104 FINAL ASSIGNMENT
  • LIOW CHUN GUAN 0351029PROFESSIONAL PPRACTICE ARC 62604 FINAL PROJECT
  • SEVENTH SCHEDULE: MAXIMUM TRAVEL DISTANCEMEASUREMENT OF TRAVI UBBL 140(3G) THE MAXIMUM TRAVEL DISTANCES SHALL BE AS SPECIFIED IN THE SEV EXITS TO BE ACCESSIBLE AT ALL TIMES
  • EL DISTANCE TO EXITSTO EXITS AND DEAD END LIMITS ENTH SCHEDULE OF THESE BY LAWS EXIT ROUTE
  • DISABLED ACCESSIBILITYEXTINGUISHING SYSTEM FIRE ALARM
  • DRAFT SUBMISSIONDESIGN PROJECT ECHOES SACRED ECHOES IS AN IMMERSIVE CULTURAL EXPERIENCE CENTRE INSPIRED BY THE NINE EMPEROR GODS FESTIVAL AND THE PHILOSOPHY OF YIN AND YANG LOCATED IN ROYAL KLANG TOWN, THE PROJECT AIMS TO PRESERVE AND REINTERPRET LOCAL CULTURAL HERITAGE THROUGH INTERACTIVE EXHIBITIONS RITUAL-INSPIRED SPATIAL EXPERIENCES, TRADITIONAL CRAFT WORKSHOPS LEARNING SPACES AND COMMUNITY GATHERING AREAS. THE DESIGN CREATES A CONTEMPORARY PLATFORM FOR CULTURAL EDUCATION ENGAGEMENT AND CONTION WHILE STRENGTHENING APPRECIATION BETWE TRADITION
  • Page 2705 CONCLUSION
  • REFLECTIVE ESSAYTHIS PROFESSIONAL PRACTICE MODULE HAS PROVIDED ME WITH A DEEPER UNDERSTANDING OF THE RESPONSIBILITIES AND REALITIES OF BECOMING A PROFESSIONAL INTERIOR DESIGNER. THROUGHOUT THE SEMESTER, I GAINED VALUABLE KNOWLEDGE BEYOND THE DESIGN PROCESS, INCLUDING BUILDING BY-LAWS, PROFESSIONAL ETHICS, LICENSING REQUIREMENTS, CONSULTANCY PRACTICE, BUSINESS MANAGEMENT, AND STATUTORY SUBMISSION PROCEDURES. EACH ASSIGNMENT CHALLENGED ME TO THINK CRITICALLY, CONDUCT THOROUGH RESEARCH, AND APPLY INDUSTRY STANDARDS IN A PRACTICAL CONTEXT. WORKING ON THESE PROJECTS HAS STRENGTHENED MY ABILITY TO CONNECT CREATIVE DESIGN WITH PROFESSIONAL PRACTICE. I REALISED THAT SUCCESSFUL INTERIOR DESIGN IS NOT ONLY ABOUT CREATING
  • Page 2906 E-PORTFOLIO LINK
Text of this page

SEVENTH SCHEDULE: MAXIMUM TRAVEL DISTANCE

MEASUREMENT OF TRAVI UBBL 140(3G) THE MAXIMUM TRAVEL DISTANCES SHALL BE AS SPECIFIED IN THE SEV

EXITS TO BE ACCESSIBLE AT ALL TIMES

EXITS MUST BE WITHIN TRAVEL DISTANCE LIMITS (SEVENTH SCHEDULE) AND ALWAYS EASILY ACCESSIBLE.

  • UBBL
  • SITE SAFETY
  • 140(3G)
  • SM11 +1PT
  • IMPLEMENT SITE AMENITIES PLAN
  • LIMIT WHEN ALTERNATIVE EXITS ARE AVAILABLE
  • PURPOSE GROUP
  • ONE-WAY TRAVEL
  • TWO-WAY TRAVEL
  • CORRIDORp. 1
  • UN-SPRINKLERED (M)
  • SPRINKLERED (M)
  • DEAD-END LIMIT (M)
  • DEAD-END LIMIT (M)
  • V SHOPp. 15
  • 45p. 15
  • 7156p. 3
  • VII PLACE OF
  • 60p. 15
  • ASSEMBLY

MEASUREMENT OF TRAVEL DISTANCE TO EXITS MAXIMUM TRAVEL DISTANCES AND DEAD-END LIMITS ARE AS STATED IN THE SEVENTH SCHEDULE OF THE UBBL.

FIRE APPLIANCES ACCESS

FIRE APPLIANCES ACCESS ROAD MUST HAVE A MINIMUM OVERHEAD CLEARANCE OF 4.5 M.

  • UBBL
  • UBBL 165(4)
  • 140(3G)
  • FIRE APPLIANCES ACCESS

FIRE APPLIANCES ACCESS

FIRE APPLIANCES ACCESS MUST BE AT LEAST 6 M WIDE ALONG 140(3A) ITS ENTIRE LENGTH AND ACCOMMODATE FIRE TRUCKS, LADDERS, TURNTABLES, AND PLATFORMS.

FIRE APPLIANCES ACCESS ROAD AND PATH TO ACCESS OPENINGS 140(3D) MUST BE FREE FROM ANY OBSTRUCTION, INCLUDING BUILDINGS, PLANTS, TREES, OR FIXTURES.

  • JALAN RAYA TIMUR
  • UBBL
  • UBBL
  • MECHANICAL VENTILATION AND AIR CONDITIONING

NATURAL LIGHTING AND VENTILATION

ALL ROOMS (EXCEPT IN HOSPITALS AND SCHOOLS) MUST HAVE WINDOWS PROVIDING NATURAL LIGHT AND VENTILATION.

• WINDOW AREA MUST BE AT LEAST 10% OF THE ROOM'S FLOOR AREA.

AT LEAST HALF OF THAT WINDOW AREA MUST BE OPENABLE FOR FREE AIRFLOW.

UBBL

UBBL

SPACES MUST HAVE AN ALTERNATIVE VENTILATION METHOD THAT CAN SUPPLY THE REQUIRED FRESH AIR WITHIN 30 MINUTES IF THE AIR-CONDITIONING SYSTEM FAILS.

AIR-CONDITIONED

HEIGHT OF ROOMS IN OTHER BUILDINGS

HEIGHT OF ROOMS IN RESIDENTIAL BUILDINGS, SHOPHOUSES, SCHOOLS, ETC

WALKWAY

IN BUILDINGS, THE HEIGHT OF ROOMS ON THE GROUND FLOOR SHALL NOT BE LESS THAN 3 METRES, AND ON ANY FLOOR ABOVE THE GROUND FLOOR SHALL NOT BE LESS THAN 2.75 METRES.

  • UBBL
  • UBBL
  • SHOPHOUSES:

• GROUND FLOOR ROOMS: ≥ 3.0 M

GROUND FLOOR PLAN

UPPER FLOOR ROOMS: ≥ 2.5 M

IF UPPER FLOOR DEPTH > 10.5 M: HEIGHT ≥ 2.55 M

  • DIMENSIONS OF BUILDINGS AND COMPARTMENTS
  • SPACE LIGHT VENTILATION
  • LIMIT OF A DIMENSION
  • NATURAL LIGHT
  • OCCUPANT LOAD PER SQM
  • PURPOSE GROUP
  • DOOR OUTSIDE
  • HORIZOTAL EXIT
  • RAMP MAIN RAMP SECOND
  • STAIRS
  • TOTAL WINDOW x100%
  • EXIT
  • EXIT
  • TOTAL CLEAR FLOOR AREA
  • 65.6SQM
  • V SHOP x100%
  • 640.54SQM
  • OTHER FLOORS
  • 6 GROSS
  • 9520MM ROOF LVL
  • VII PLACES OF ASSEMBLY
  • 1.5 NET
  • 7250MM $LAB LVL
  • VENTILATION
  • STAIRS

DESIGNATION OF PURPOSE GROUPS

EACH UPPER FLOOR MUST HAVE AT LEAST TWO STAIRCASES (EXCEPT BY-LAW 194). STAIR WIDTH MUST SUPPORT FULL FLOOR OCCUPANCY IF ONE STAIRCASE IS BLOCKED, WITH CONSISTENT WIDTH THROUGHOUT. HANDRAILS CAN ENCROACH UP TO 80 MM. DOORS MUST NOT SWING INTO THE REQUIRED STAIR OR LANDING WIDTH.

  • TOTAL WINDOW x100%
  • TOTAL CLEAR FLOOR AREA
  • UBBL
  • FF LVL FR 3750MM
  • 20.1SQM 640.54SQM x100%
  • GF SLAB LVL
  • HANDRAILS
  • RISER
  • 1700мм
  • HANDRAILS
  • THREAD
  • UBBL

1. STAIRCASES WITH 2-4 RISERS MUST HAVE AT LEAST ONE HANDRAIL.

2. STAIRCASES > 2200 MM REQUIRE INTERMEDIATE HANDRAILS EVERY 2200 MM.

3. IN NON-RESIDENTIAL BUILDINGS, STAIRCASES ≥ 1100 MM WIDE REQUIRE HANDRAILS ON BOTH SIDES.

• HANDRAIL HEIGHT: FROM TREAD NOSING: 825-900 MM

  • GF LVL EB150MM FELBONM ROAD LVL
  • 300MM
  • ISSUE
  • SOLUTION
  • HANDRAIL

CURRENT VENTILATION PERCENTAGE: 3.14% MINIMUM VENTILATION PERCENTAGE: 4%

  • INCREASE THE NUMBER OF OPENABLE WINDOW
  • 900мм
  • PURIFICATION CHAMBER

AT LANDINGS: MINIMUM 900 MM o PROJECTION FROM WALL: MAXIMUM 100 MM

LENGTH